Home » Products » Aerial Cable/Overhead Cable » 1kV Insulated Aerial Cable
inquiry form

1kV Insulated Aerial Cable

Standards
The 1kV insulated aerial cable is produced in accordance with GB/T12527-2008 standard: aerial insulated cables of rated voltage up to and including 1kV. On the other hand, it also meets our enterprise standard.

Operating Conditions
1. Rated voltage U0/U: 0.6/1kV
2. Max. operating temperature of conductor for long-term application: 70℃ for PVC or PE insulated type, and 90℃ for XLPE insulated type
3. Min. ambient temperature when laying: -20℃.
4. Bending radius: If the outer diameter of cable is less than 25mm, the bending radius should be larger than 4 times of outer diameter. If the outer diameter is 25 mm or higher, the bending radius should not be less than 6 times of outer diameter.

Applications
This product is weatherproof PVC, PE or XLPE insulated aerial cable with copper core, aluminum core or aluminum alloy core, and it is applicable for overhead power lines with rated voltage of 1kV AC and below.

Model Code
JK: Aerial cable
LH: Aluminum alloy
YJ: XLPE insulation
L: Aluminum
Y: PE insulation

Model Explanations
Model Names Main Usages
JKV-0.6/1 Cu core PVC insulated overhead cable with rated voltage of 0.6/1kV They are used as fixed overhead cable, service drop, etc.
JKLV-0.6/1 Al core PVC insulated overhead cable with rated voltage of 0.6/1kV
JKLHV-0.6/1 Aluminum alloy core PVC insulated overhead cable with rated voltage of 0.6/1kV
JKY-0.6/1 Cu core PE insulated overhead cable with rated voltage of 0.6/1kV
JKLY-0.6/1 Al core PE insulated overhead cable with rated voltage of 0.6/1kV
JKLHY-0.6/1 Aluminum alloy core PE insulated overhead cable with rated voltage of 0.6/1kV
JKYJ-0.6/1 Cu core XLPE insulated overhead cable with rated voltage of 0.6/1kV
JKLYJ-0.6/1 Al core XLPE insulated overhead cable with rated voltage of 0.6/1kV
JKLHYJ-0.6/1 Aluminum alloy core XLPE insulated overhead cable with rated voltage of 0.6/1kV
Specifications
Model Core Number Rated Voltage 0.6/1KV
Nominal Cross Section (mm2)
JKV, JKLV, JKLHV, JKY, JKLY 1 16~240
JKLHY, JKYJ, JKLYJ, JKLHYJ 2, 4 10~120
JKLV, JKLY, JKLYJ 3+K 10~120

Note: K represents load carrying neutral conductor, and its section can be selected freely to match with the main core to satisfy the requirements of power distribution project.

Technical Parameters
Nominal Cross Section of Conductor (mm2) Conductor Resistance at 20℃ (≤Ω/km) Min. Insulation Resistivity at Rated Operating Temperature (MΩ·km) Cable Breaking Strength (≥N)
Cu Core Al Core Aluminum Alloy Core 70℃ 90℃ Hard Cu Core Al Core Aluminum Alloy Core
Hard Cur Soft Cu
10
16
25
35
50
70
95
120
150
185
240
1.906
1.198
0.749
0.540
0.399
0.276
0.199
0.158
0.128
0.1021
0.0777
1.83
1.15
0.727
0.524
0.387
0.268
0.193 0.153
-
-
-
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
3.574
2.217
1.393
1.007
0.744
0.514
0.371
0.294
0.239
0.190
0.145
0.0067
0.0065
0.0054
0.0054
0.0046
0.0040
0.0039
0.0035
0.0035
0.0035
0.0034
0.67
0.65
0.54
0.54
0.40
0.40
0.39
0.35
0.35
0.35
0.34
3471
5486
8465
11731
16502
23461
31759
39911
49505
61846
79823
1650
2517
3762
5177
7011
10354 1
37207
17339
21033
26732
34679
2514
4022
6284
8800
12569
17596
23880
30164
37706
46503
60329
Other Parameters
Nominal Cross Section of Conductor (mm2) Calculated Outer Diameter (mm) Calculated Weight (kg/km)
Cu Core Al Core
10
16
25
35
50
70
95
120
150
185
240
6.5
8.0
9.5
11.0
12.5
14.0
16.5
18.0
20.0
22.5
25.5
106.0
169.0
264.0
360.0
518.0
734.0
998.00
1241.0
1565.0
1926.0
2485.0
94.0
143.0
197.0
270.0
337.0
443.0
606.0
730.0
909.0
1127.0
1459.0

Test Method
1. Electrical property: GB3048-1994
2. Mechanical property: GB/T4909-1985
3. Mechanical and physical properties: GB2951

Requirements for Delivery
The delivery length is negotiable, and the metering error of length should be no more than 0.5%.

Related Names